ME Series Off-Grid Inverter
ME Series Low-Frequency Inverter/Charger 0.4-4 kW
Parameter | ME0512 | ME0812 | ME1012/24 | ME1312/24 | ME1512/24 | ME2012/24/48 | ME2524/48 | ME3024/48 | ME3824/48 | ME5024/48
Power input | 220 VAC (standard) / 110 VAC (custom)
Input voltage range | 220 V model: 154-264 VAC ±3 V (normal) / 185-264 VAC ±3 V (UPS); 110 V model: 77-132 VAC ±3 V (normal) / 92-132 VAC ±3 V (UPS)
The ME series belongs to the off-grid solar inverters range. Review the exact model in the specification table rather than selecting on the series name alone.
Parameter | ME0512 | ME0812 | ME1012/24 | ME1312/24 | ME1512/24 | ME2012/24/48 | ME2524/48 | ME3024/48 | ME3824/48 | ME5024/48 Power input | 220 VAC (standard) / 110 VAC (custom)
Structural Features
Key features of the ME platform:
- Parameter | ME0512 | ME0812 | ME1012/24 | ME1312/24 | ME1512/24 | ME2012/24/48 | ME2524/48 | ME3024/48 | ME3824/48 | ME5024/48
- Power input | 220 VAC (standard) / 110 VAC (custom)
- Input voltage range | 220 V model: 154-264 VAC ±3 V (normal) / 185-264 VAC ±3 V (UPS); 110 V model: 77-132 VAC ±3 V (normal) / 92-132 VAC ±3 V (UPS)
- Input frequency | 50/60Hz±5%
- Rated output power | 400W | 640W | 800W | 1000W | 1200W | 1600W | 2000W | 2400W | 3000W | 4000W
Product Advantages
Parameter | ME0512 | ME0812 | ME1012/24 | ME1312/24 | ME1512/24 | ME2012/24/48 | ME2524/48 | ME3024/48 | ME3824/48 | ME5024/48
Power input | 220 VAC (standard) / 110 VAC (custom)
Input voltage range | 220 V model: 154-264 VAC ±3 V (normal) / 185-264 VAC ±3 V (UPS); 110 V model: 77-132 VAC ±3 V (normal) / 92-132 VAC ±3 V (UPS)
Input frequency | 50/60Hz±5%
Rated output power | 400W | 640W | 800W | 1000W | 1200W | 1600W | 2000W | 2400W | 3000W | 4000W
For a ME quotation, send the exact model, quantity, destination market, electrical requirements and expected operating duty. Identify any branding, packaging or documentation requirements separately so the supplied configuration is clear.
Technical Parameters
| Parameter | ME0512 | ME0812 | ME1012/24 | ME1312/24 | ME1512/24 | ME2012/24/48 | ME2524/48 | ME3024/48 | ME3824/48 | ME5024/48 |
|---|---|---|---|---|---|---|---|---|---|---|
| Power input | 220 VAC (standard) / 110 VAC (custom) | |||||||||
| Input voltage range | 220 V model: 154-264 VAC ±3 V (normal) / 185-264 VAC ±3 V (UPS); 110 V model: 77-132 VAC ±3 V (normal) / 92-132 VAC ±3 V (UPS) | |||||||||
| Input frequency | 50/60Hz±5% | |||||||||
| Rated output power | 400W | 640W | 800W | 1000W | 1200W | 1600W | 2000W | 2400W | 3000W | 4000W |
| Output voltage (utility mode) | Same as input voltage (bypass) | |||||||||
| Output frequency (utility mode) | Same as input frequency (bypass) | |||||||||
| Output voltage (inverter mode) | 220VAC±10% (110VAC±10%) | |||||||||
| Output frequency (inverter mode) | 50 or 60 Hz ±1% | |||||||||
| Output waveform (inverter mode) | Sine wave | |||||||||
| Battery type | External lead-acid, flooded or lithium battery | |||||||||
| Battery voltage | 12VDC / 24VDC / 48VDC | |||||||||
| Battery charge voltage | 13.7VDC / 27.4VDC / 54.8VDC | |||||||||
| Max. PV array power | 12 V: 400 W; 24 V: 800 W | 12 V: 800 W; 24 V: 1600 W; 48 V: 3200 W | ||||||||
| PV input voltage range (PWM/MPPT) | 12 V: PWM 15-50 VDC; 24 V: PWM 30-60 VDC (no built-in MPPT) | 12 V: MPPT 15-150 / PWM 15-50 VDC; 24 V: MPPT 30-150 / PWM 30-105 VDC; 48 V: MPPT 60-150 / PWM 60-105 VDC | ||||||||
| Max. PV array open-circuit voltage | 12 V: PWM 50 VDC; 24 V: PWM 60 VDC | 12 V: MPPT 150 / PWM 50 VDC; 24 V: MPPT 150 / PWM 105 VDC; 48 V: MPPT 150 / PWM 105 VDC | ||||||||
| Optimal Vmp range | 12 V: PWM 15-20 VDC; 24 V: PWM 30-40 VDC | 12 V: MPPT 15-105 / PWM 15-20 VDC; 24 V: MPPT 30-105 / PWM 30-40 VDC; 48 V: MPPT 60-105 / PWM 60-80 VDC | ||||||||
| Max. solar charging current | 30A | 60A | ||||||||
| Max. AC charging current | 10A | 16A | 19/10A | 24A/12A | 29A/15A | 66/33/16 A (default 53/26/13 A) | 41 A (default 33 A) / 20 A (default 16 A) | 50 A (default 40 A) / 25 A (default 20 A) | 63 A (default 50 A) / 31 A (default 25 A) | 83 A (default 66 A) / 41 A (default 33 A) |
| Transfer time | <=10 ms (UPS mode) / <=20 ms (INV mode) | |||||||||
| Peak load ratio | 3:1 (max.) | |||||||||
| Transformer | Toroidal transformer | |||||||||
| Standby power (W) | 12 V: 8 W; 24 V: 16 W; 48 V: 32 W | |||||||||
| Protection (utility mode) | Utility mode: input overcurrent protection via no-fuse breaker (MCB) | Utility mode: input overcurrent protection via air circuit breaker | ||||||||
| Protection (inverter mode) | Inverter mode: overload, short-circuit, low-voltage and battery reverse-polarity protection (fuse) | |||||||||
| Display | Color segment LCD with LED indicators | |||||||||
| Display pages | Paging key scrolls AC voltage / frequency, PV voltage / current, output voltage / frequency, battery voltage, load current, etc. | |||||||||
| LED indicators | LEDs indicate utility, charging, inverting and fault status | |||||||||
| Audible alarm | Buzzer distinguishes fault codes by long/short beep patterns | |||||||||
| Operating temperature | -10 to 50 °C | |||||||||
| Storage temperature | -15 to 45 °C | |||||||||
| Noise level | <45 dB | |||||||||
| Dimensions L×W×H (mm) | 325×263×128 mm | 360×316×298 mm | ||||||||
Use the ME electrical limits as the starting point for system design. Confirm the AC supply where applicable, battery voltage, PV string limits and equipment connected to the output. Optional functions must be specified with the order.
Check the battery and charging requirements for the selected ME model. Match permitted charge and discharge current, charging profile and any supported BMS protocol. A matching connector or nominal voltage alone does not confirm compatibility. For a battery-free or DC-only product, use only the interfaces listed in its model table.
For a ME quotation, send the exact model, quantity, destination market, electrical requirements and expected operating duty. Identify any branding, packaging or documentation requirements separately so the supplied configuration is clear.
The table describes one published model revision. Confirm the current supply configuration before ordering.
Before You Order
Use the ME electrical limits as the starting point for system design. Confirm the AC supply where applicable, battery voltage, PV string limits and equipment connected to the output. Optional functions must be specified with the order.
Electrical Match
Check the battery and charging requirements for the selected ME model. Match permitted charge and discharge current, charging profile and any supported BMS protocol. A matching connector or nominal voltage alone does not confirm compatibility. For a battery-free or DC-only product, use only the interfaces listed in its model table.
Installation Plan
Install the ME product within the temperature, ventilation and enclosure conditions stated in its manual. Specify cable sizes, isolation and protection through a qualified installation design. Product dimensions and clearances should be checked before cabinet or mounting work.
Supply Configuration
ME Series — Selection and Application
The ME series belongs to the off-grid solar inverters range. Review the exact model in the specification table rather than selecting on the series name alone.
Parameter | ME0512 | ME0812 | ME1012/24 | ME1312/24 | ME1512/24 | ME2012/24/48 | ME2524/48 | ME3024/48 | ME3824/48 | ME5024/48 Power input | 220 VAC (standard) / 110 VAC (custom)
Model selection
For ME, first identify the required electrical interface and continuous load.
Parameter | ME0512 | ME0812 | ME1012/24 | ME1312/24 | ME1512/24 | ME2012/24/48 | ME2524/48 | ME3024/48 | ME3824/48 | ME5024/48 Power input | 220 VAC (standard) / 110 VAC (custom)
Operating features
Parameter | ME0512 | ME0812 | ME1012/24 | ME1312/24 | ME1512/24 | ME2012/24/48 | ME2524/48 | ME3024/48 | ME3824/48 | ME5024/48
Power input | 220 VAC (standard) / 110 VAC (custom)
Input voltage range | 220 V model: 154-264 VAC ±3 V (normal) / 185-264 VAC ±3 V (UPS); 110 V model: 77-132 VAC ±3 V (normal) / 92-132 VAC ±3 V (UPS)
Input frequency | 50/60Hz±5%
Rated output power | 400W | 640W | 800W | 1000W | 1200W | 1600W | 2000W | 2400W | 3000W | 4000W
System integration
Use the ME electrical limits as the starting point for system design. Confirm the AC supply where applicable, battery voltage, PV string limits and equipment connected to the output. Optional functions must be specified with the order.
Battery and charging
Check the battery and charging requirements for the selected ME model. Match permitted charge and discharge current, charging profile and any supported BMS protocol. A matching connector or nominal voltage alone does not confirm compatibility. For a battery-free or DC-only product, use only the interfaces listed in its model table.
Installation planning
Install the ME product within the temperature, ventilation and enclosure conditions stated in its manual. Specify cable sizes, isolation and protection through a qualified installation design. Product dimensions and clearances should be checked before cabinet or mounting work.
Monitoring and interfaces
Check which monitoring ports and communication options are included on the selected ME model. Confirm accessory hardware, protocol and firmware before relying on remote monitoring, battery communication or expansion.
Frequently asked questions
Which ME model should I choose? Start with the model table and the loads or battery system, then confirm the final configuration before ordering.
Are all optional functions included? No. Availability depends on the model, hardware and agreed supply specification.
Can I combine data from different catalogues? Use one matching model and revision. Confirm any differing values with the supplier.
Discuss your requirements
Contact Techfine Group with your ME requirements. Include the model and the application so the electrical configuration and supporting documents can be checked.